How much refrigerant can a small recovery tank hold?

How much refrigerant can a small recovery tank hold?

NEVER Exceed Refrigerant Recovery Tank Limits By law, a tank can only be filled to 80% capacity and must be kept under 122°F. It is recommended to fill to 2 lbs less than the 80%. For example, a 30 lb cylinder can hold 22 lbs of refrigerant and a 50 lb cylinder can hold 38 lbs of refrigerant.

How much does a freon recovery tank weigh?

Tech Specs

Item Refrigerant Recovery Cylinder
Weight Empty (Lb.) 15.6
Height (In.) 17 15/16 in
Width (In.) 9 1/16 in
Collar 7 1/2

Can a recovery tank explode?

Also, tanks that are more than 80% full (DOT violation) may expose the technician to high concentrations of vented refrigerant, and severely overfilled tanks can possibly explode.

How full can you fill a refrigerant recovery tank?

Do Not Overfill the Recovery Cylinder Typically the cylinder should not be filled to more than 80% liquid full at 77°F. Another guideline is to not exceed the gross weight (total weight of the container and its contents).

How long is a recovery tank good for?

Per DOT regulations, recovery cylinder certification expires five years from the date of manufacture. By the five-year mark, the recovery cylinder must be certified by a facility approved by DOT. When a cylinder is recertified, the recertification date is marked on the cylinder in one of two ways.

What does WC mean on recovery tank?

Next, look for a stamp that says WC. This value indicates the tank’s water capacity, the total weight in liquid water to fill the tank 100%.

How do you calculate refrigerant weight?

Divide the quantity of refrigerant that the heat pump moves by the time it takes to move it. If it pumps 3.6 kilograms of refrigerant in 10 seconds: 3.6 / 10 = 0.36 kilograms per second.

What happens if you overfill a refrigerant tank?

Overfilled storage containers may explode due to liquid refrigerant expanding when heated. Transportation of refrigerant stor- age cylinders more than 80% full is a DOT violation.

How often does a reusable container for refrigerant need to be hydrostatically tested?

Reusable refrigerant containers that are normally under any pressure above 15 psig, must be hydrostatically tested and date stamped every 5 years.

How do I know if my recovery tank is full?

The water capacity of a recovery cylinder normally is stamped on the outside of the cylinder. For example, if a recovery cylinder has a water capacity of 47.17 pounds, then its internal volume will be 0.75 cubic feet (47.17 pounds ÷ 62.5 pounds/cubic foot = 0.75 cubic feet).

How much does a recovery tank weigh when full?

You get 22.95 lbs to fill the tank completely.

How much refrigerant can I safely store in a recovery tank?

CPS Products Recovery Tanks are trusted by refrigerant technicians for safely storing 30-90 lbs of refrigerant. Browse our options below:

How much does a recovery tank weigh?

50 lb(22.7kg) recovery tank – Fill with no more than 32lbs(14.5kg) of R410a or 39 lbs(17.7kg) of R22 – total tank weight will be about 60lbs(27.2kg) for R410a and 67lbs(30.4kg) for R22. Now for the details.

Where can I find other refrigerants for my mastercool recovery tank?

You can find other refrigerants by looking up their datasheets. A 30lb (13.6kg) Mastercool 400 PSI (27.57 bar) recovery tank has a water capacity of 26.2 lbs. Divide that by the water density of 62.42, and you get 0.419 cubic ft of space in the tank (25.2/62.42 = 0.419)

How much space is in a mastercool 400 psi recovery tank?

A 30lb (13.6kg) Mastercool 400 PSI (27.57 bar) recovery tank has a water capacity of 26.2 lbs. Divide that by the water density of 62.42, and you get 0.419 cubic ft of space in the tank (25.2/62.42 = 0.419)